Extension Cord Gauge Calculator
Type the watts or amps and the cord length and get the thinnest extension cord gauge that stays within its rating and a 5% voltage drop, or a plain “no cord” for heaters, fridges and air conditioners.
100% in your browser — nothing uploadedWhat gauge extension cord you need for 1,500 watts, 50 feet and other loads
| Cord | Its rating at this length | Voltage drop (there and back) | Verdict |
|---|
Paid link 14 gauge extension cords, 50 ft, on Amazon →
We earn a commission if you buy, at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.
How the calculator picks a gauge
Quick answer: a 1,500-watt load on a 50-foot cord at 120 volts needs 14 AWG. It draws 12.5 amps (1,500 ÷ 120). A 16-gauge cord is rated 13 amps up to 50 feet, but it would lose 6.1 volts there and back, 5.1% of the supply, while 14 AWG loses 3.8 volts (3.2%). At 25 feet 16 AWG is enough, and at 100 feet you need 12 AWG. The exception is the most searched load of all: a 1,500-watt space heater takes no extension cord, according to CPSC, NFPA and the heater makers, so the calculator says so instead of giving a gauge.
The method is the one SLAC, a U.S. Department of Energy laboratory, publishes for its own cords: the current stays within the cord’s ampacity in the National Electrical Code’s flexible-cord table (Column B: 13 amps for 16 AWG, 18 for 14, 25 for 12, 30 for 10), and the voltage drop at the nameplate amps stays within 5%, with copper resistance at 75 °C from the National Bureau of Standards’ copper wire tables (now NIST). The calculator also caps a 120-volt cord at the 15 amps its plug carries and uses the lower rating cords get past 50 feet (10 amps for 16 AWG, 13 for 14 AWG), the way Southwire tags its own. Published charts disagree because each one assumes something different: the guide below shows where.
Extension cord gauge chart by amps and length (120 V)
The thinnest cord that stays within its rating and a 5% voltage drop at 120 V, with copper at 75 °C. Find the amps on the label (watts ÷ 120) and round up to the next row: a 1,500 W load is 12.5 A, so use the 13 A row.
| Load | 10 ft | 25 ft | 50 ft | 75 ft | 100 ft | 150 ft |
|---|---|---|---|---|---|---|
| 3 A (360 W) | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 16 AWG |
| 5 A (600 W) | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 14 AWG |
| 8 A (960 W) | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 14 AWG | 12 AWG |
| 10 A (1,200 W) | 16 AWG | 16 AWG | 16 AWG | 14 AWG | 12 AWG | 12 AWG |
| 12 A (1,440 W) | 16 AWG | 16 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG |
| 13 A (1,560 W) | 16 AWG | 16 AWG | 14 AWG | 14 AWG | 12 AWG | 10 AWG |
| 15 A (1,800 W) | 14 AWG | 14 AWG | 14 AWG | 12 AWG | 12 AWG | 10 AWG |
When the answer is no extension cord
| Appliance | What the makers or agencies say |
|---|---|
| Space heater | Directly into a wall outlet, never an extension cord or power strip: CPSC (January 2026), NFPA, the U.S. Fire Administration, and the Lasko, Dyson and Utilitech manuals. |
| Refrigerator or freezer | No extension cord: Whirlpool and Frigidaire manuals. One Samsung freezer manual (2014–15) allows a 3-wire grounding cord marked 10 A or more. |
| Window or portable air conditioner | No extension cord, and most rule out surge protectors and multi-outlet adapters: GE, LG, Haier and Frigidaire. |
| Microwave, air fryer and other cooking appliances | NFPA: never use an extension cord for a cooking appliance. GE’s microwave page, Panasonic, Hamilton Beach and Cosori allow a cord whose marked rating is at least the appliance’s. |
| Washer or dehumidifier | No extension cord: Whirlpool’s washer page and Frigidaire’s dehumidifier manual. NFPA: never with a major appliance. |
| Electric car charger | NFPA: never use a multiplug adapter or extension cord with an electric vehicle charger. |
| Air compressor | Use extra air hose instead of an extension cord: Makita’s manual. |
From a portable generator the cord can’t be avoided. CPSC says to use heavy-duty cords made for outdoor use, with a wattage rating that exceeds the total of everything plugged into them and a plug with all three prongs, long enough to keep the generator outdoors, far from windows, doors and vents. CPSC also warns never to use a male-to-male cord. NFPA estimates that extension cords were involved in about 1,780 US home fires a year in 2015–2019, with 110 deaths.
Why extension cord charts disagree
Every chart keys on the nameplate amps, but each one sets a different limit. Here is what the ones we read give for a 15 A load:
| Source | 15 A at 50 ft | 15 A at 100 ft | What it assumes |
|---|---|---|---|
| This calculator | 14 AWG | 12 AWG | SLAC’s method, plus the 15 A plug and the lower rating past 50 ft |
| SLAC (DOE laboratory, 2025) | 14 AWG | 12 AWG | NEC ampacity and a 5% drop at the nameplate amps |
| WC Safety (2026) | 14 AWG | 12 AWG | The cord rating, the 15 A plug and a 5% drop |
| Grainger selection guide | 14 AWG | 12 AWG | Not stated |
| DeWalt manual | 12 AWG | Not recommended | Not stated |
| Milwaukee manual | 12 AWG | No size listed | A 5-volt drop at 150% of the rated amps |
| Southwire’s tags | 14/3 tagged 15 A | 12/3 tagged 15 A; most 14/3 tagged 13 A | The rating printed on the cord |
The tag is a heating limit, not a voltage-drop limit: a 100 ft 14/3 cord tagged 13 A loses about 6.7% of the voltage at 13 A. That is why the calculator can say a cord is within its tag and still too long.
Voltage drop by gauge and length for a 1,500 W load
Volts lost at 12.5 A and 120 V. The formula: 2 × length in feet × amps × ohms per 1,000 ft ÷ 1,000. The copper tables give 4.89 ohms per 1,000 ft for 16 AWG at 75 °C, 3.07 for 14, 1.93 for 12 and 1.215 for 10. On 240 V the same cord loses the same volts at the same amps, which is half the percentage.
| Cord | 25 ft | 50 ft | 100 ft |
|---|---|---|---|
| 16 AWG | 3.1 V (2.5%) | 6.1 V (5.1%) | 12.2 V (10.2%), over its rating |
| 14 AWG | 1.9 V (1.6%) | 3.8 V (3.2%) | 7.7 V (6.4%) |
| 12 AWG | 1.2 V (1.0%) | 2.4 V (2.0%) | 4.8 V (4.0%) |
| 10 AWG | 0.8 V (0.6%) | 1.5 V (1.3%) | 3.0 V (2.5%) |
What the tag says: usual ratings by gauge
| Cord | Up to 50 ft | Over 50 ft |
|---|---|---|
| 16 AWG (16/3) | 13 A, 1,625 W | 10 A, 1,250 W |
| 14 AWG (14/3) | 15 A, 1,875 W | 13 A, 1,625 W |
| 12 AWG (12/3) | 15 A, 1,875 W | 15 A, 1,875 W |
| 10 AWG (10/3) | 15 A, 1,875 W | 15 A, 1,875 W |
Usual tags on 120 V cords, from Southwire’s catalog and StayOnline’s table, which it credits to UL; the watts are amps × 125 V, the rated voltage. CPSC says to check the rating on the tag on the cord or its packaging, and that cords should be at least 16 AWG unless they are 18 AWG with fuse protection. Your cord’s tag always wins over this table.
Christmas lights, the outdoors and power strips
For lights, add up the watts on each strand’s tag. CPSC says never to string together more than three sets of incandescent lights, and NFPA says to read the maker’s instructions for how many strands to connect. Outdoors, use lights, cords and outlets marked for outdoor use; CPSC’s 1990 advice adds that it is good practice to plug into an outlet protected by a ground-fault circuit interrupter.
UL calls a power strip “just an extension cord with a lot of outlets”, and its guide says to plug in only one heat-producing appliance, such as a toaster or a hair dryer, per strip. The calculator works for a strip at the end of a cord: add up the watts of everything plugged into it.
220–230 V cords in mm²
Pick mm² and 220 or 230 V in the calculator (at 220 V the same cord loses a slightly larger share of the voltage). Metric cords follow IEC cord classes, here as summarised by the component maker Schurter: above 2 m, 1 mm² for 10 A and 1.5 mm² for 16 A. IEC 60884-2-7, the standard for extension sets, stops at 16 A. At 230 V:
| Load | 3 m | 5 m | 10 m | 15 m | 20 m | 30 m |
|---|---|---|---|---|---|---|
| 3 A (690 W) | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² |
| 6 A (1,380 W) | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² |
| 8 A (1,840 W) | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² |
| 10 A (2,300 W) | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1 mm² | 1.5 mm² |
| 13 A (2,990 W) | 1.5 mm² | 1.5 mm² | 1.5 mm² | 1.5 mm² | 1.5 mm² | 1.5 mm² |
| 16 A (3,680 W) | 1.5 mm² | 1.5 mm² | 1.5 mm² | 1.5 mm² | 1.5 mm² | 2.5 mm² |
Sources
Read on November 14, 2026: SLAC’s power cord requirements (SLAC-I-730-0A11S-006-R001, July 25, 2025); NBS Handbook 100, Copper Wire Tables (1966); NEC Table 400.5(A)(1) as reprinted by MSHA and reproduced in 2025 and 2026 (the current NFPA text needs a login and was not read); CPSC publication 5032, its 2008 Home Electrical Safety Checklist, its 2021 portable generator alert, its March 31, 2026 warning on male-to-male cords and its January 2026 winter release; NFPA’s 2026 Educational Messages Desk Reference and its 2022 report on electrical fires; the U.S. Fire Administration’s portable heater flyer; UL’s guide to power strips; Southwire’s cord catalog; StayOnline (November 30, 2023); WC Safety (August 16, 2026); Grainger’s extension cord selection guide; the DeWalt DCA120, Milwaukee 2845-20, Makita compressor and Toro blower manuals; the heater, refrigerator and air conditioner manuals named above and the Panasonic microwave, Hamilton Beach coffee maker and Cosori air fryer manuals; Schurter on IEC cord classes. UL 817 and the current NEC are paywalled and were not read.
FAQ
What gauge extension cord do I need for 1,500 watts?
At 120 V, 16 AWG up to 25 ft, 14 AWG for a 50 ft cord and 12 AWG for 100 ft. 1,500 W draws 12.5 A; at 50 ft a 16-gauge cord would lose 5.1% of the voltage, over the 5% the calculator allows. If the 1,500 W is a space heater, though, CPSC says to plug it straight into a wall outlet, never into an extension cord.
Can you plug a space heater into an extension cord?
No. CPSC (January 2026), NFPA and the U.S. Fire Administration all say to plug a space heater directly into a wall outlet, never into an extension cord or power strip, and so do the Lasko, Dyson and Utilitech heater manuals we read. The older advice to use a heavier cord comes from CPSC releases of 1988 (#14 or #12 for heaters) and 1999 (“special, heavy duty” cords), not from today’s guidance.
Can I use an extension cord with a refrigerator or a window air conditioner?
Their manuals say no: Whirlpool and Frigidaire for refrigerators and freezers; GE, LG, Haier and Frigidaire for window units. NFPA says never to use one with a major appliance. A portable generator is the exception, because it has to run outdoors at least 20 feet from the home: CPSC says to use heavy-duty outdoor cords whose wattage rating exceeds the total of what you plug in. Tick the generator box to size that cord.
Is 12 or 14 gauge better for an extension cord?
The smaller number is the thicker wire. 12 AWG carries more and loses less voltage, so it is never worse, only heavier and dearer. For a 15 A load, 14 AWG is enough up to 50 ft and 12 AWG up to 100 ft: at 100 ft a 14-gauge cord would lose 7.7% of the voltage, and 14/3 cords that long are usually tagged 13 A.
What do 16/3 and SJTW mean on an extension cord?
16/3 is three wires of 16 AWG: hot, neutral and ground. The letters describe the jacket. In Southwire’s catalog, S is extra-hard service (600 V) unless J follows it, J is hard service (300 V), T is thermoplastic, O is oil resistant and W is outdoor. CPSC says to use only a cord marked for outdoor use outdoors.
How long can an extension cord be?
None of the US agencies we read (CPSC, NFPA, OSHA) sets a maximum length, but every foot adds voltage drop: a 16-gauge cord at 100 ft loses 6.5% at 8 A. StayOnline, a cord maker, says cords over 100 ft aren’t UL listed without a special investigation. Type the length you need and use the gauge the calculator gives for it.
Why do extension cord charts disagree?
They assume different things. SLAC and WC Safety keep the voltage drop within 5% at the nameplate amps, Milwaukee sizes for a 5-volt drop at 150% of the rated amps, and a cord’s tag is a heating limit: at its full tag, a 100 ft 14/3 cord loses 6.7% of the voltage and a 100 ft 16/3 cord 8.1%. So for 15 A at 50 ft, Grainger, Southwire’s tags and WC Safety allow 14 AWG, while DeWalt and Milwaukee want 12. The calculator shows its arithmetic, so you can see which rule a cord passes.